Sign In | Join Free | My chinacsw.com |
|
Brand Name : ANGES
Model Number : 85HP
Place of Origin : China
MOQ : 1
Payment Terms : T/T, L/C
Delivery Time : 25 days
Packaging Details : Plywood case
Refrigerant : R404a
Cooling capacity : 65.56kw at water outlet -25 ℃
Compressor : Piston Compressor
Condenser : Finned copper tube
Evaporator : Plate heat exchanger
Condition : Brandnew
Name : Glycol water chiller
Application : Glycol beer chiller, Low temperature chiller for soft drinks containing carbonic acid gas
85Ton Air Cooled Chiller Glycol Water Chiller Low Temperature Screw type cooler Laboratory Low Temperature Circulation
Low Temperature Glycol Chiller
Low temperature chiller generally refers to the temperature below zero or more than 100 degrees below zero chiller. The refrigerated substances are generally ethanol, alcohol, salt water and so on.
With the continuous development trend of high-tech, low-temperature chiller is an indispensable key machine and equipment in high-tech manufacturing industry.
Specification
Model Parameter | AGS-085ASL | |
Nominal cooling capacity | kcal/h | 56330 |
kw | 65.5 | |
Input power | kw | 92.5 |
Max. Running current | A | 210 |
Power supply | 3PH~415V/50HZ | |
Refrigerant | Type | R404A |
Refrigerating circuit | 1 | |
Type of control | Expansion valve | |
Compressor | Type | Semi-hermetic screw |
Quantity | 1 | |
Power | 79 | |
Start-up mode | Y-△ | |
Capacity control | 0-25-50-75-100 | |
Condenser | Type | Air cooled type finned copper tube |
Cooling air flow (m3/h) | 91000 | |
Power(kw) | 13.5 | |
Evaporator | Type | Plate type |
Quantity | 1 | |
Chilled fluid flow (m3/h) | 47.8 | |
Inlet and outlet pipe diameter (inch) | 4 | |
Safety protection | compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, anti-freezing | |
Net weight | kg | 2420 |
Dimension | mm | 3150*2140*2200 |
The nominal cooling capacity is according to: Inlet chilled fluid temperature: -20℃,outlet chilled fluid temperature: -25℃
Main uses of low temperature chiller:
The proportion of Ethylene Glycol Aqueous Solution of glycol water chiller unit
Operating temperature | Concentration | Density | Specific heat capacity | Heat conductivity | Viscosity | Freezing point |
℃ | % | ×10³ Kg/m³ | KJ/(kg.k) | W/m.k | Pa.s | ℃ |
0 | 25 | 1.03 | 3.834 | 0.511 | 3.8 | -10.6 |
-10 | 35 | 1.063 | 3.561 | 0.4726 | 7.3 | -17.8 |
-20 | 45 | 1.08 | 3.312 | 0.441 | 21 | -26.6 |
-30 | 55 | 1.097 | 2.975 | 0.3725 | 90 | -41.6 |
![]() |
85Ton Glycol Low Temperature Chiller Screw Type for Laboratory Images |